GCS type low-voltage withdrawable switchgear

GCS type low-voltage withdrawable switchgear

summary

The GCS type low-voltage withdrawable switchgear is suitable for power distribution systems in various industries, including power plants, oil, chemical, metallurgy, textiles, and high-rise buildings. It is particularly suitable for large power plants and petrochemical systems where high automation is required and interfaces with computers are essential. This equipment is designed for power distribution, centralized motor control, and reactive power compensation in power supply systems, featuring a three-phase AC frequency of 50 (60) Hz, rated working voltages of 400V and 660V, and rated currents up to 5000A.

The design of the device complies with the following standards: IEC439-1 "Low Voltage Complete Switchgear and Control Equipment" GB7251 "Low Voltage Complete Switchgear".

Use environmental conditions

◆ The ambient air temperature is not higher than +40℃, not lower than-5℃, and the average temperature within 24 hours shall not be higher than +35℃. If it exceeds, the operation shall be reduced according to the actual situation;

◆ Indoor use, the altitude of the place of use shall not exceed 2000m;

◆ The relative humidity of the surrounding air should not exceed 50% at the highest temperature of +40℃, and a larger relative humidity is allowed at lower temperatures, such as 90% at +20℃. Consider the effect of condensation that may occur accidentally due to changes in temperature;

◆ The inclination of the device to the vertical plane shall not exceed 5° during installation, and the whole cabinet column shall be relatively flat (in accordance with GBJ232-82 standard);

◆ The device shall be installed in a place without violent vibration and impact, and not enough to cause undue corrosion of electrical components;

◆ When the user has special requirements, it can be negotiated with the manufacturer.

Main technical parameters

 

order number

name

parameter

1

Rated voltage of main circuit (V)

Rated AC 400/660

2

Rated voltage of auxiliary circuit

Alternating current 220,380 (400), DC 110,220

3

rated frequency Hz

50(60)

4

Rated insulation voltage (V)

660

 

5

rated current A

horizontal bus

≤5000

rated current A

Vertical bus (MCC)

1000

6

Rated short-time withstand current of busbar (KA/1s)

50,80

7

Rated peak withstand current of busbar (KA/0.1s)

105,176

 

8

Power frequency test voltage (V/1min)

main circuit

2500

accessory circuit

2000

 

9

 

generatrix

three-phase four-wire system

A.B.C.PEN

Three phase five wire system

A.B.C.PE.N

10

levels of protection

IP30.IP40


outline overall and installing dimensions

 7a65534d6f7a6b7135313771425a54775759764544513d3d.png

 (mm)

 

Cabinet width (D)

Cabinet depth (W)

Cabinet height (H)

600,800,1000

800,1000

2200

 

 ordering instruction

Factory data and accessories

When placing an order, the user should provide:

Main circuit distribution system diagram and plan layout, rated working voltage, rated working current, protection device setting current and necessary technical parameters.

Mark the specifications of incoming and outgoing cables.

The model, specification and quantity of the main electrical components in the switchgear.

If busbar bridge or busbar trough is needed between switch cabinets or incoming cabinets, the span and height from the ground should be indicated

Provide specific requirements data.

When switchgear is used in special environmental conditions, it should be specified in detail when ordering.

Switch cabinet surface color and other specific requirements.

The manufacturer shall provide the following documents and attachments when supplying

dispatching list

Product certificate and factory test report

operating instruction

Related electrical drawings

Description of main components

Door key, operating handle and spare parts specified in the contract.